31.11 Model 463G NET with CELL as Alternate Primary and Dialer Backup, Standard or
Encrypted Line Security
StandardorEncryptedLineSecurityisprovidedusingNETcommunicationwithCELLasanalternateprimary
andwithdigitaldialerasabackup.XR500networkcommunicationisusedasprimarywitha6minute
check-inwhenarmed,andarandomcheck-inovera60minuteperiodwhendisarmed.CELListhebackup
pathandsettodailytest.ShouldtheNETprimarypathbecomedisabled,CELLadaptsthesamecheck-in
timeprogrammedfortheprimarycommunicationandbecomesanalternateprimarypath.Thedialerpath
isusedasthebackupifbothNETandCELLfailtoreceiveacknowledgementfromthereceiver.
ThismethodofoperationcausestheCELLalternateprimarytoadapttothe6minuteNETprimarycheck-in
ratewhentheNETprimaryisunavailablemaintaininglinesupervisionandprecludestheneedforacentral
stationrunnertorespondtotheNETprimaryfailure.
Path 1 programming Path 2 programming Path 3 programming
CommType:=NET CommType:=CELL Comm Type: = DD
Path Type: = Primary PathType:=Backup(operates
as alternate primary)
PathType:=Backup
(operates as second
method)
TestRpt:=NO TestRpt:=YES TestRpt:=YES
Checkin:=6minute,orRND
(random)
Test Freq: = Daily Test Freq: = Daily
FailTime:=6minute,orRND
(random)
Checkin: = ADAPT DuplicateAlarms:=YES
Encrypt:=NOorYES* Encrypt:=NOorYES*
SubCode:=YES SubCode:=Shared
*ForEncryptedLineSecurity,programaPassphraseinNetworkOptions.
31.12 Model 463G NET with CELL as Backup and Adaptive Primary, Standard or
Encrypted Line Security
StandardorEncryptedLineSecurityisprovidedwhenprogrammedusingNETcommunicationandCELLas
backup and as needed adapts and takes over as primary. XR500 network communication is used as primary
witha6minutecheck-inwhenarmed,andarandomcheck-inovera60minuteperiodwhendisarmed.
CELListhebackuppathandsettodailytest.Shouldtheprimarypathbecomedisabled,theCELLadapts
toaspecial3minutecheck-intimeandbecauseofthatcheck-inratebecomestheprimarywithoutthe
requirementofabackup.ThismethodofoperationcausestheCELLbackuptoadapttothe3minutecheck-
inratewhentheNETprimaryisunavailablebecomingastandaloneprimarywithouttheneedforabackup.
ThismaintainslinesupervisionandprecludestheneedforacentralstationrunnertorespondtotheNET
primaryfailure.
Path 1 programming Path 2 programming
CommType:=NET CommType:=CELL
Path Type: = Primary PathType:=Backup(operatesassecond
method)
TestRpt:=NO TestRpt:=YES
Checkin:=6minute,orRND
(random)
Test Freq: = Daily
FailTime:=6minute,orRND
(random)
Checkin:=ADAPT3
Encrypt:=NOorYES* Encrypt:=NOorYES*
SubCode:=YES DuplicateAlarms:=YES
SubCode:=Shared
*ForEncryptedLineSecurity,programaPassphraseinNetworkOptions.