XT Series Programming Guide Digital Monitoring Products
19
SYSTEM OPTIONS
9.7 Cross Zone Time
Enter the time allowed between zone faults. When a zone programmed for cross zoning
faults, the panel begins counting down the Cross-Zone Time entered here. If the same
zone or another cross-zoned zone faults within this time, an alarm report is sent to the
receiver.
If the Cross-Zone Time expires without the second zone fault, only a zone fault report
from the rst zone is sent to the receiver. The Cross-Zone Time can be from 4 to 250
seconds in one second increments. Enter 0 (zero) to disable the Cross-Zone Time
feature. See the Appendix.
9.8 Power Fail Delay
This option tracks the duration of an AC power failure. The delay time can be from 1
to 9 hours. When the AC power is off for the length of the programmed delay time, an
AC power failure report is sent to the receiver. For example, if the power failure delay
is set for two hours, then the AC power failure report will be sent between 2-3 hours.
Entering a 0 (zero) sends the AC power failure report within 15 seconds.
9.9 Swinger Bypass Trips
Enter the number of times (1-6) a zone can go into an alarm or trouble condition within
one hour be fore being auto matically bypassed. Bypassed zones are auto matically reset
when the area they are assigned to is disarmed. All 24-hour zones are reset when any
area of the system is dis armed. A programming Stop operation restores a bypassed zone.
Entering 0 (zero) disables this function. Default is 2.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires before
the trip counter is exceeded, the trip counter returns to 0 (zero). If the trip counter is
exceeded before the hour expires, the zone is auto matically bypassed by the panel. A
Bypass Re port is sent to the receiver if Bypass Re ports is YES.
9.10 Reset Swinger Bypass
When YES is selected, an auto matically bypassed zone is reset if it remains in a normal
condition for one complete hour after being bypassed. A report of the automatic reset is
sent to the receiver if Bypass Reports has been se lected as YES. Default is NO.
9.11 Telephone Access
YES allows the use of standard DTMF telephones to arm and disarm and check the armed
status of the XT30/XT50 panel. Refer to the XT30 or XT50 User’s Guide for complete
information.
9.12 Zone Activity Hours
This option provides supervision of a person living alone for non-activity. Enter the
number of hours, 0 to 9, allowed to elapse without a disarmed zone being tripped before
a message is sent to the receiver. Default is 0 (zero).
When the system is disarmed, the timer begins to countdown the number of hours
programmed. Each time activity occurs, the timer restarts the countdown.
Before the countdown time expires, the keypad sounds a tone and PRESS ANY KEY
displays to allow the user to restart the activity timer. The duration of the tone is the
number of seconds programmed for Entry Delay 2.
Select the SUPV/TRBL receiver option in communication programming to send S93
ALARM: User Activity Not Detected, S94 Alert: Activity Check Enabled, and S95 Alert:
Activity Check Disabled messages.
When an open/close schedule is programmed, the timer only counts down during the
scheduled open period. Also, when a schedule is programmed, if the timer is counting
down and the scheduled open time occurs, the timer resets and begins the countdown
again.
CRS ZONE TM: 0
PWR FAIL HRS: 1
SWGRBYPS TRIPS: 2
RST SBYP NO YES
PHONE ACC NO YES
ZN ACTY HRS: 0