Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
14
ComplIanCe
Reset Jumpers J16
14.1 Description
A pair of jumper wires are located at the top right of the panel circuit board labeled RESET. Momentarily
shorting these jumper wires allows you to reset the microprocessor. Resetting the panel allows you to enter
the panel’s internal programmer.
To reset the panel when rst installing the system, place the blade of a slotted screwdriver across the two
reset jumper wires after applying power to the panel.
To reset the panel while the system is operational (for example, prior to reprogramming), you can short the
jumper wires without powering down the system.
After resetting the panel for programming, you must begin within 30 minutes. If you wait longer than 30
minutes, you will have to reset the panel again.
J4
RED
PROG
J8
XRSuper6/XR20/XR40
Command Processor™ Panel
J16
Reset
J7
RJ SUP
AC
1
2
3
4567
8
10
11 12 13 14
15
16 17 18
19
9
20
21
22 23
24
25 26
+B
BELL
GND
SMK
RED
YEL
GRN
BLK
Z1
Z2 Z3 Z4
Z5
Z6
Z7
Z8 Z9
Z10-
AC
-B
GND
GND
GND
GND
Z10+
Phone Jack
Connector
Momentarily touch J16 jumper
wires with a screwdriver blade
to reset the panel.
Figure 8: XRSuper6, XR20, XR40 Panel Showing the Reset Jumper Wires
Universal Burglary Specications
15.1 Introduction
The programming and installation specications contained in this section must be completed when installing
the XRSuper6/XR20/XR40 in accordance with any of the UL burglary standards. Additional specications may
be required by a particular standard.
15.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70, UL 681, and UL 611 for all burglary installations.
15.3 Police Station Phone Numbers
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specically provided for that purpose.
15.4 Bypass Reports
The bypass reports must be programmed as YES for all UL burglary applications. See LT-0305.
15.5 System Maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
15.6 Cross-Zoning
Zones used for cross zoning must detect the same event and shall not conict with UL 681 or 1641.
15.7 Ground Start
Ground Start phone lines must not be used for UL listed systems.
15.8 Listed Receivers
Operation has been veried with the DMP SCS-1R Security Receivers, Sur-Gard MLR2-E, SG-HLR2-DG, FBII
CP220PB, Osborne-Hoffman Quick-Alert, and Radionics D6500 receivers.