Digital Monitoring Products XTL Series Guide d'installation Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 16
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
Digital Monitoring Products XTL/XTLC Installation Guide
8
COMPLIANCE
Central Station Burglar Alarm Units
ANSI/UL 1610
17.1 Supervision
CommercialBurglaryisprovidedwhentheCellCheck-inandFailTimetimeissetto3minutes.
Note:TheSecureComWirelesstextplanselectedforthepanelshouldmatchorexceedtheprogrammed
MonthlyLimitoradditionalcellularchargesmayapply.
17.2 Remote Disarm
REMOTEDISARMmustbeprogrammedasNO.
17.3 Central Station
MESSAGETOTRANSMITprogrammingforzonesmustnotbesettoLOCAL(L).
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
18.1 Bell Output Denition
ThewirelesssirenoftheXTL/XTLCpanelmustbeprogrammedtooperatesteadyonburglaryalarmsand
temporalonrealarms.SeetheXTL/XTLCProgrammingGuide(LT-1108).
18.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
18.3 Wireless Supervision Time
TheZoneInformationSupervisionTimemustbe3minutesforredevices.SeetheXTL/XTLCProgramming
Guide.
18.4 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.
18.5 Wired Modules
ModulesthatconnecttothePROGheader,suchasthe738Z,mustnotbeusedsincethebatterystandby
timewillbereducedbelowthe24hourminimum.