Digital Monitoring Products, Inc.
1912XR Programming
Page 14
6.1 This function allows you to select the reports the 1912XR sends to the SCS-1
Receiver.
6.2 ABORT REPORT - YES allows the panel to send an alarm abort report to the
receiver any time an alarm report has also been sent and the bell is still
sounding. The area must be disarmed and no alarmed loops can still be armed.
Abort reports are also sent when the system is disarmed during Transmit Delay
and the Bell Output is active. See section 3.5.
6.3 BYPASS REPORTS - YES allows the panel to send all loop bypasses, resets,
and force arm reports to the receiver. The bypass report includes the loop
number, loop name, and the user number of the individual operating the system.
6.4 SCHEDULE CHANGE REPORTS - YES allows the panel to send all permanent
and temporary, primary and secondary, schedule changes to the receiver. The
report includes the day, opening time, closing time, and the user number of the
individual making the change.
6.5 CODE CHANGE REPORTS - YES allows the panel to send all code additions,
changes, and deletions to the receiver. The code change report includes the user
number added or deleted and the user number of the individual making the
change.
6.6 ACCESS KEYPADS - Enter the Security Command keypad addresses that send
door access reports to the receiver. A report is sent with each door access made
from the selected keypads. Keypads at addresses not selected still operate the
door strike relay but do not send door access reports. The report includes the
user number and the keypad address used.
6.7 AMBUSH - YES allows an ambush report to be sent anytime user code number
one is entered at a Security Command keypad. Selecting NO disables the
ambush report and allows user code number one to operate the same as all
other codes.
There is one Ambush code available for each active partition programmed into
the panel.
ABORT NO
SYSTEM REPORTS
CODE CHG YES
BYPASS YES
SCHD CHG YES
AMBUSH NO
ACS KEY: - - - - - - - -