Digital Monitoring Products 1912XR Guide d'installation Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 12
1912XR Installation Guide
Powered Loop for 2-Wire Smoke Detectors
11.1 Terminals 12 and 13
A resettable 2-wire Class B powered loop is provided on terminals 12 (positive) and 13 (negative) of the
panel. For programming purposes the loop number is 5. The loop uses a Model 309, 3.3K EOL resistor
provided with the panel and has an operating range of 8.8 to 14.2 VDC. The UL compatibility identifier is:
A. The following detectors are compatible with the 1912XR and 715 Loop Expander powered loops:
Protection Loops
12.1 Description
Terminals 14 to 19 are the four burglary loops. For programming purposes, the loop numbers are 1 to 4.
Terminals 14 to 19 provide connection as described below.
Terminal Function
14 Loop 1 voltage sensing
15 Ground for Loops 1 & 2
16 Loop 2 voltage sensing
17 Loop 3 voltage sensing
18 Ground for Loops 3 & 4
19 Loop 4 voltage sensing
The voltage sensing terminal measures the voltage flowing through a 1k End Of Line resistor to ground.
Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-open) with any
of the burglary protection loops.
Mfg Model
Detector
I D
Base
Base
I D
# of
Detector
s
SS 1151 A B110LP or B116LP 10
SS 2151 A B110LP or B116LP 10
SS 1400 A 12
SS 1451 A B401 or B401B A 10
SS 1451DH A DH400 A 10
SS 2400, 2400TH A 10
SS 2451, 2451TH A B401 or B401B A 10
SS 2451 A DH400 A 10
DS DS200/DS200HD A MB200-2W A 15
DS DS250/DS250TH B MB2W/MB2WL A 10
ESL 422C/422CT S10P 25
ESL 429C/429CT S09A 12
ESL 422CRT/422CST S11A 12
HOC SLK-12 HD-4 HSB - 12 - 1 HB-80 18
RA-400 MAY BE USED ON ALL BRK DETECTORS
USE 330 OHM RESISTOR IN MB200-2W BASE
DIFFERENT DETECTOR MODELS MAY NOT BE MIXED
Figure 6: Compatible 2-wire smoke detectors
1K
NORMALLY CLOSED CONTACTS NORMALLY OPEN CONTACTS COMBINATION: NORMALLY OPEN AND
NORMALLY CLOSED CONTACTS
1K
1K
Figure 7: Protection loop contact wiring