Digital Monitoring Products 9000 Series Installation Guide
6
Site cOde
POSitiOn: 1
Site Code Position
Enter the site code start position in the data string. Press any Select key to enter a number
between 0-255. Default is 1.
Site cOde
Length: 8
Site Code Length
Enter the number of characters the site code contains. Press any Select key to enter a number
between 1-16. Default is 8.
USer cOde
POSitiOn: 9
User Code Position
Dene the User Code start bit position. Press any Select key to enter a number between 0-255.
Default is 9.
USer cOde
Length: 16
User Code Length
Dene the number of User Code bits. Press the fourth Select key to enter a custom number.
Custom numbers can only be a number between 16-32. Press COMMAND to save the entry. The
default is the DMP value of 16.
reqUire Site
cOde: nO YeS
Require Site Code
Press the top row Select key under YES to use a site code and press COMMAND to view the site
code entry display. Default is NO.
Note: A card with a site code greater than three digits cannot be used. Use only cards with
three-digit site codes.
Site cOdeS 1-4
> > > >
Site Codes 1-4
Enter site codes 1-4 (left to right separated by > sign). Press the Select key below the > sign to
add, delete, or change the site code and press COMMAND. Site code range is 0-999. Press the
COMMAND key to display SITE CODES 5-8.
Site cOdeS 5-8
> > > >
Site Codes 5-8
Enter site codes 5-8 (left to right separated by > sign). Press the Select key below the > sign to
add, delete, or change the site code and press COMMAND. Site code range is 0-999.
degrAded MOde
Degraded Mode
Note: The Degraded Mode option appears in programming, but does not currently apply to the
9000 Series Keypad.
Accessing Keypad Diagnostics
If necessary, refer to Accessing Installer Options earlier in this document.
KPd KPd KPd
OPt diAg rF StOP
Keypad Diagnostics (KPD DIAG)
The Keypad Diagnostic option allows you to check the display segments, keyboard backlighting
and test individual keys.
Press the Select key under KPD DIAG. The keypad lights all display segments and illuminates
the keyboard in Red. In approximately one second the keyboard backlighting changes to
Green. The keypad alternates between these two states for approximately two minutes. Press
COMMAND at any time to begin testing individual keys.
PreSS KeY tO
teSt
Test Individual Keys
The display changes to PRESS KEY TO TEST. This option tests each key on the keyboard to
ensure it is operating properly. Press and hold each key for about two seconds. The key number
being held appears in the display. Verify the correct number displays before testing the next
key.
inPUt WiegAnd
Input Wiegand (9063 only)
This option tests the internal input from proximity credentials. The display shows OKAY each
time a good proximity read is received.
Accessing Keypad Wireless Survey
Access the Installer Options Menu through the User Options function. Hold down the Back Arrow and COMMAND keys for
two seconds to display SET BRIGHTNESS. Enter the code 3577 (INST) and press COMMAND.
KPd KPd KPd
OPt diAg rF StOP
Keypad Wireless Survey (KPD RF)
Press the Select key under KPD RF to start the RF communication survey test. The keypad logo
turns on Red indicating communication has not been established with the panel receiver. When
successful communication has been established, the keypad logo turns Green.
rF SUrVeY
Note: The keypad RF survey is a good option to use during the keypad association programming
by the control panel. The backlit logo turns Green to indicate that it has been associated by
the panel.
Exiting the Installer Options
When done, press the COMMAND key once to return to the Installer Options screen. Press the Select key under STOP to exit
the Installer Options function.