XR100 Series Canadian Installation Guide Digital Monitoring Products
9
InstallatIon
Secondary Power Supply
6.1 Battery Terminals 3 and 4
Connect the black battery lead to the negative
battery terminal. The negative terminal connects to
the enclosure ground internally through the XR100
Series circuit board. Connect the red battery lead to
the battery positive terminal. Observe polarity when
connecting the battery.
You can add a second battery in parallel using the DMP
Model 318 Dual Battery Harness. DMP requires each
battery be separated by a PTC in the battery harness
wiring to protect each battery from a reversal or
short within the circuit. See Figure 4.
Use sealed lead-acid batteries only: Use
the DMP Model 365 (12 Vdc 9 Ah), Model 366
(12 Vdc 18 Ah), Model 368 (12 Vdc 5.0 Ah), or
Model 369 (12 Vdc 7 Ah) sealed lead-acid
rechargeable battery. Batteries supplied by DMP have been tested to ensure proper charging with DMP products.
GELCELLBATTERIESCANNOTBEUSEDWITHTHEXR100SERIESPANEL.
6.2 Earth Ground (GND)
Toprovidepropertransientsuppression,XR100Seriespanelterminal4mustbeconnectedtoearthgroundusing
14gaugeorlargerwire.DMPrecommendsconnectingtoacoldwaterpipe,groundrod,orbuildinggroundonly.Donot
connect to an electrical ground or conduit, sprinkler or gas pipes, or to a telephone company ground.
6.3 Battery Only Restart
WhenpoweringuptheXR100SeriespanelwithoutACpower,brieyshortacrossthebatterystartpadstopullinthe
battery cutoff relay. The leads need a momentary short only. Once the relay has pulled in, the battery voltage holds it
in that condition. If the XR100 Series panel is powered up with an AC transformer, the battery cutoff relay is pulled in
automatically. For more information refer to Figure 1.
6.4 Battery Replacement Period
DMP recommends replacing the battery every 3 to 5 years under normal use.
6.5 Discharge/Recharge
TheXR100Seriesbatterychargingcircuitoatchargesat13.9Vdcatamaximumcurrentof1.0Ampsusinga
50 VA or 56 VA transformer. Listed below are the various battery voltage level conditions:
Battery Trouble: Below 11.9 Vdc
Battery Cutoff: Below 10.2 Vdc
Battery Restored: Above 12.6 Vdc
6.6 Battery Supervision
TheXR100SeriesteststhebatterywhenACpowerispresent.Thetestisdoneeverythreeminutesandlastsforve
seconds. During the test, the panel places a load on the battery; if the battery voltage falls below 11.9 Vdc a low battery
is detected. If AC power is not present, a low battery is detected any time the battery voltage falls below 11.9 Vdc.
If a low battery is detected with AC power present, the test repeats every two minutes until the battery charges above
12.6 Vdc indicating the battery has restored voltage. If a weak battery is replaced with a fully charged battery, the
restored battery will not be detected until the next two minute test is completed.
6.7 Battery Cutoff
The panel disconnects the battery any time the battery voltage drops below 10.2 Vdc. This prevents battery deep
discharge damage.
AC
1234
+BAC –B
Battery
Start
318 Battery
Harness
Panel Red and
Black Battery Cables
Red
Black
Battery
Battery
Battery
318 Battery
Harness
Red
Black
AC
Canadian
Panel
C
C
B
1 t
art rnd
Bell
Crct
Figure 6: Wiring Multiple Batteries