Digital Monitoring Products XR100 Series Canadian Installation Guide
16
InstallatIon
Dry Contact Relay Outputs
12.1 Description
The XR100 Series panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model 305 relays in
socketsK6(Output1)andK7(Output2)andaModel431OutputHarnessontheJ24-pinHeader.Eachrelayprovidesone
SPDT set of contacts that can be operated by any of the functions listed below:
1) Activation by zone condition: Steady, Pulsing, Momentary, and Follow
2)Activationby24-hour7-dayschedule:Oneonandoneofftimeadayforeachrelay
3) Manual activation from the DMP LCD keypad menu
4)Communicationfailure 8)ExitandEntrytimers
5) Armed area annunciation 9) System Ready
6) Fire Alarm or Fire Trouble or Supervisory 10) Late to Close
7) Ambush Alarm
RefertotheXR100SeriesCanadianProgrammingGuide(LT-0896CAN)forspecicinformation.
12.2 Contact Rating
The Model 305 relay contacts are rated for 1 Amp at 30 Vdc (allows .35 power factor). Connect auxiliary power to the
Relay Output 1 common terminal by installing the gray harness wire to terminal 7. Current draw for all connected devices
must not exceed the panel maximum current rating.
12.3 Model 431 Output Harness Wiring
TherelaycontactsareaccessiblebyinstallingtheDMP431OutputHarnessonthe4-pinheaderlabeledJ2.Output2
uses the top three prongs, and Output 1 uses the bottom three prongs. The wire harness and contact locations are shown
below:
Contact Color
Output 1 normally closed Violet
Output 1 common Gray
Output 1 normally open Orange
Output 2 normally closed Violet with white stripe
Output 2 common Whitewithgraystripe
Output 2 normally open Orange with white stripe
The relay contacts must be connected to devices located within the same room as the XR100 Series panel.
Annunciator Outputs
13.1 Description
The four programmable annunciator outputs can be programmed to indicate the activity of the panel zones or conditions
occurring on the system. Annunciator outputs do not provide a voltage but instead switch-to-ground a voltage from
another source. The outputs can respond to any of the conditions listed in the Description section for Dry Contact Relays.
Maximum voltage is 30 Vdc @ 50mA.
13.2 Model 300 Harness Wiring
AccesstheopencollectoroutputsbyinstallingDMP300Harnessonthe4-pinheaderlabeledJ11.Theoutputlocationsare
shown below. For UL applications, devices connected to the outputs must be located within the same room as the panel.
Output Color Wire Output Color Wire
3 Red 1 5 Green 3
4 Yellow 2 6 Black 4
13.3 Model 860 Relay Module
Connect a Model 860 Relay Module to the J11 on the XR100 Series Canadian panel to provide relays for outputs 3-6. Use
these relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various
functions. Power is supplied to the relay coils from a single wire connected to the panel auxiliary power terminal 7. The
module includes one relay and provides three additional sockets for expansion of up to four relays. Mount the 860 inside
thepanelenclosureusingthe3-holepatternandplasticstandoffs.Refertothe860ModuleInstallSheet(LT-0484)as
needed.
Relay Contact Rating: 1 Amp at 30 Vdc (allows .35 power factor)