Digital Monitoring Products Canadian XR100 Guide d'installation Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
XR100 Series Canadian Installation Guide Digital Monitoring Products
3
IntroductIon
3.2 Wiring Diagram
The XR100 Series Canadian panel diagram below shows some of the accessory modules you can connect for use in various
applications.Abriefdescriptionofeachmodulefollowsinsection3.4.
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range: 9.7 VDC to
14.0 VDC.
Class B (Style A).
WARNING: Incorrect
connections may cause
damage to the unit.
Bell
12 VDC
Minimum cutoff time 15 min.
1.5 Amp Max
Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
Front and Rear
tamper protection
included with
Model 350A
Attack Resistant
Enclosure.
Bell cutoff time
range is 5 to 99
minutes, non-coded.
Minimum voltage on Auxiliary output to
process Sensor trips is 10.2 VDC.
Auxiliary/Smoke Power
Total current combined from
terminals 7, 11, 25, and 27
1.5 Amp Max 10.2 VDC to 14.0 VDC
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDRED YEL GRN BLKZ1Z2Z3Z4Z5Z6Z7Z8 Z9+ Z9– Z10+ Z10–AC –B GND GND GNDGND
K6 K7
Output 1Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1 Out2
Outputs 3-6
J11
3
4
5
6
J2
¼"
J1
Ethernet
R
L
X
Link LED
Activity LED
OVC
XR100 Series
Command Processor™
Panel
1k Ohm 1k Ohm 1k Ohm
DISARM
ARM
Smoke
Detector
3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm
1k Ohm
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Annunciator Outputs (J11)
Output Color Code
Output 3 Red
Output 4 Yellow
Output 5 Green
Output 6Black
Front
Tamper
Rear
Tamper
s
16 to 18 gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
Cold Water
Pipe Earth
Ground
Bell
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
3.3k
Ohm
Resistor
3.3k
Ohm
Resistor
Zone Expander
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Use Listed Power Supervision
Relay rated at 12 VDC.
1k Ohm
s
= Supervised Circuit
Zone
9
Zone
10
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
1k Ohm 1k Ohm 1k Ohm
Zone Expander
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
RED
YELLOW
GREEN
BLACK
RED
s
s
s
s s s s s
s
The plug-in transformer shall plug
into a 120 VAC 60 Hz outlet not
controlled by a switch and all
16 to
18 gauge wire
shall run through
conduit.
s
s
s
S S S S S S S S
S S S S
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
S S
S SS SS S
1k Ohm
Zone Expander
(up to 8 zones)
Model 712-8
19mA @ 12
VDC
S S
Zone
Expander
Model 711
7mA @ 12
VDC
1k
Ohm
s
Keyswitch Arming
can be connected
to any zone. See
LT-0681
s
s
s
s s
s s
s
Earth Ground
s
s
s
SIA CP-01-2010 minimum
system is XR100, listed local
Bell, and off premise DACT
communication to an SCS-1R
receiver plus listed compatible
keypads as indicated in the
installation guide.
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN TO
PROVIDE SUPERVISION OF CONNECTIONS.
Figure 1: XR100 Series Canadian panel Wiring Diagram
3.3 Lightning Protection
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR100 Series Canadian panel
input and output circuits. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning Suppressors.
Vue de la page 8