1912XR Installation Guide
Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 13
12.2 Operational parameters
Each burglary protection loop detects three conditions: open, normal, and short.
The parameters for each are listed below:
Condition Resistance on loop Voltage on right terminal
Open over 1300 ohms over 2.0 VDC
Normal 600 to 1300 ohms 1.2 to 2.0 VDC
Short under 600 ohms under 1.2 VDC
12.3 Loop response time
A condition must be present on a loop for 500 milliseconds (1/2 second) before it's detected by the 1912XR
panel. Make sure any detection devices you use on the protection loops are rated for use with this delay.
Loops can also be programmed for a Fast Response delay of 160 milliseconds.
12.4 Keyswitch arming loop (maintained)
Programming a loop as an Arming Type, allows selected areas to arm when the loop is placed into a short
condition. The selected areas disarm when the loop is placed into a normal (1K EOL) condition. If placed
into an open condition from a normal (disarmed ) condition, a trouble is reported. If placed into an open
condition from a short (armed) condition, an alarm is reported and the loop is disabled until another
disarming occurs within the system. The areas controlled by the loop and the relay outputs that indicate
their armed or disarmed status are selected in the panel's Programmer.
Dry Contact Relay Outputs
13.1 Description
Two Form C (SPDT) relay outputs can be provided on the 1912XR by installing two DMP Model 305 relays
into the sockets labeled K9 (Output 1) and K5 (Output 2). Both relays can be operated by the functions
listed below:
1) Activation by loop condition
Steady
Pulsing
Momentary
Follow
2) Activation by 24 hour 7 day schedule
One on and one off time a day for each relay
3) Manually from the Security Command keypad User Menu
4) Communication failure output
5) Armed area annunciation
6) Fire Alarm or Fire Trouble
7) Other system conditions. See the 1912XR Programming Manual (LT-0171).
13.2 Contact rating
The DMP 1912XR relay contacts are rated for 1 Amp at 30 VDC or 0.5 Amp at 120 VAC. The auxiliary
output power from terminal 7 can be internally connected to the common terminal of Relay Output 1 by
installing the J15 jumper across both pins.
13.3 Harness wiring
The relay contacts are accessible by installing the DMP 304 Harness on the 10-pin header labeled J2. The
contact locations are shown below:
Contact Color Wire
Output 1 normally closed Violet 10
Output 1 common Gray 9
Output 1 normally open Orange 8
Output 2 normally closed Violet 7
Output 2 common Gray 6
Output 2 normally open Orange 5
The relay contacts must be connected to devices located within the same room as the 1912XR panel.