26.6 Supervised Remote Relay
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
DMP part #DI-0001 Rectifier
(1N4001 diode) in series with
input from Model 866 terminal 6.
10k EOL
Resistor
DMP Model 308
Indicating Circuit Module
DMP Model 866
37mA at 12 VDC
1k
Normally Open
contacts will
close on alarm.
Normally Closed
contacts will
open on alarm.
DPDT Relay
Use Model ASRB-1 from Advanced Signaling
or Model RBSN-TTL from Altronix.
30mA coil operating current at 12 VDC.
1912XR Command Processor Panel
Model 304
Output Harness
Relay #1
N/O
Orange
1k
3.3k Resistor
DMP Model 309
1k
1k
AC BELL
AC
1
2
34 567 89
10
11
12
13
14 15
16
17 18 19
GND
RED YEL GRN BLKB + B - SMK L5+ L5- L1 L2 L3 L4GNDGND
K5
K9
J15 Jumper connects the panel's
auxiliary power to the common
wire of relay output #1.
Remote DPDT
Relay
supervised
Silence switch
Wiring between the 866 module and the DPDT relay is supervised
against opens, shorts, and grounds. Either of these trouble
conditions cause the 866 module's Bell Trouble contacts to open.
The loop connected to the Bell Trouble contacts on the 866
Indicating Circuit Module must be programmed as a Supervisory
Type Loop and selected for display in the keypad status list.
The 866 module must be installed in
the panel enclosure or in an approved
enclosure connected by conduit.
Insert a Model 305 Plug-in Relay into
the K9 socket to enable output #1.