1912XR Installation Guide
Digital Monitoring Products, Inc. 1912XR Installation Guide
Page 9
Primary Power Supply
6.1 AC terminals 1 and 2
Connect the transformer wires to terminals 1 and 2 on the panel. Use no more than 70 ft of 16 gauge, or 40
ft of 18 gauge, wire between the transformer and the 1912XR.
Always ground the panel before applying power to any devices:
The 1912XR must be properly
grounded before connecting any devices or applying power to the panel. Proper grounding protects against
Electrostatic Discharge (ESD) that can damage system components. See Earth ground.
6.2 Transformer types
The standard transformer for the 1912XR is 16.5 VAC 40VA, which provides up to 600mA of auxiliary
current. Refer to the 1912XR Wiring Diagram (LT-0182) on the panel enclosure door for a list of optional
transformers. The total current available is limited by the total battery standby requirements.
The transformer must be connected to a 120 VAC 60 Hz commercial power outlet that is not controlled by a
wall switch. Never share the transformer output with any other equipment.
The Model 320 or 322 wire-in transformers are required for NFPA 72 applications.
Secondary Power Supply
7.1 Battery terminals 3 and 4
Connect the black battery lead to terminal 4 on the panel and to the negative terminal of the battery. The
negative terminal connects to the enclosure ground internally through the 1912XR circuit board. Connect
the red battery lead to terminal 3 on the panel and to the positive terminal of the battery. Observe polarity
when connecting the battery.
You can add a second battery in parallel using the DMP Model 318 Dual Battery Harness.
Use sealed lead-acid batteries
only:
Use the DMP Model 367, 12 VDC 6.5Ah sealed lead-acid
rechargeable battery. Batteries supplied by DMP or manufactured by Eagle Picher or Yuasa have been
tested to ensure proper charging with DMP products.
GEL CELL BATTERIES CANNOT BE USED WITH THE 1912XR PANEL.
7.2 Earth ground
Terminal 4 of the 1912XR panel must be connected to earth ground using 14 gauge or larger wire to
provide proper transient suppression. DMP recommends connecting to a cold water pipe or ground rod
only. Do not connect to electrical conduit or a telephone company ground.
7.3 Battery only restart
When powering up the 1912XR panel without AC power, it's necessary to short across the CR23 leads to
pull in the battery cutoff relay. The leads need a momentary short only. Once the relay has pulled in, the
battery voltage holds it in that condition. If the 1912XR panel is powered up with an AC transformer, the
battery cutoff relay is pulled in automatically.
7.4 Replacement period
DMP recommends the battery be replaced every 3 to 5 years under normal use.
7.5 Discharge/recharge
The 1912XR battery charging circuit float charges at 13.9 VDC at a maximum current of 1.2 Amps using a
40VA transformer. The total current available is reduced by the combined auxiliary current draw from
terminals 7, 11, and 12. The various battery voltage levels are listed below:
Battery Trouble: Below 11.9 VDC
Battery Cutoff: Below 10.2 VDC
Battery Restored: Above 12.6 VDC