XRSuper6/XR20/XR40 Programming Guide
2500 N. Partnership Boulevard Springfield, MO 65803 www.dmpnet.com Digital Monitoring Products
7.5 OUTPUT ACTION
This option allows you to define the operation of the four on-board annunciator
outputs.
7.5A CUTOFF OUTPUTS
Any or all of the available outputs can be programmed here to turn off after the time
specified in OUTPUT CUTOFF TIME. See section OUTPUT CUTOFF TIME. To disable
this option, press any Select key to clear the display of output numbers and then
press COMMAND.
7.5B OUTPUT CUTOFF TIME
If a Cutoff Output is assigned, you can enter a Cutoff Time of up to 15 minutes for
the output to remain on. If the output is turned off manually, the cutoff time is
reset. The Cutoff Time can be from 1 to 15 minutes. Enter zero to provide
continuous output.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not
reset. Both outputs turn off when the original time expires.
7.5C COMMUNICATION FAILURE OUTPUT
This output is turned on when the panel fails to communicate with the receiver after
three successive dial attempts. Enter zero to disable this output.
7.5D FIRE ALARM OUTPUT
This output is turned on any time a fire type zone is placed in alarm. The output is
turned off using the Sensor Reset option while no additional fire type zones are in
alarm. Enter zero to disable this output.
7.5E FIRE TROUBLE OUTPUT
This output is turned on any time a fire type zone is placed in trouble or when a
supervisory type zone is placed in alarm or trouble. The output is turned off when
all fire and supervisory type zones are restored to normal. Enter zero to disable.
7.5F AMBUSH OUTPUT
This output is turned on any time an Ambush code is entered at a keypad. The
output is turned off using the Sensor Reset option. Enter zero to disable this output.
7.5G ENTRY OUTPUT
This output is turned on at the start of the entry delay time. The output is turned
off when the area is disarmed or the entry delay time expires. Enter zero to disable.
7.5H EXIT OUTPUT
This output is turned on any time an exit delay time starts. The output is turned off
when the system arms or when the arming has been stopped. Enter zero to disable.
7.5I READY OUTPUT
This output is turned on whenever all disarmed zones are in a normal state. The
output is turned off when any disarmed zone is in a bad state. Enter zero to disable.
7.5J ARMED OUTPUT
This output is turned on any time an area of the system is armed. The output is
turned off when the system is completely disarmed. Enter zero to disable this
output.
7.5K BURGLARY OUTPUT
This output is turned on any time a burglary zone is placed in alarm. The output is
turned off when the area in which the alarm occurred is disarmed and no other
burglary zones are in alarm. Enter zero to disable this output.
OUTPUT OPTIONS
CO OUTS: - - - -
OUTPUT ACTION . . .
CUTOFF TIME: 0
COM FAIL OUT: 0
FIRE ALR OUT: 0
FIRE TRB OUT: 0
AMBUSH OUT: 0
ENTRY OUT: 0
EXIT OUT: 0
READY OUT: 0
ARMED OUT: 0
BURGLARY OUT: 0