Digital Monitoring Products XR100 Series Programming Guide
62
Appendix
With each zone trip during the Walk Test:
• Keypaddisplayincrementseachtimeaselectedzoneisopenedorshorted
• Thekeypadbuzzesfortwoseconds
• ThepanelsoundsthealarmbellsasprogrammedinBellAction
• EachtimeaFI,FV,orSVzonetrips,aSensorResetoccurs.
If ENHANCED ZONE TESTisselectedasYES:
AVerifymessageissentatthetimethezonetripoccursinsteadofattheendof
theWalkTest.ForFI,FVorSVzonetypes,theVerifymessageissentattheinitial
trip.Forallotherzonetypes,theVerifymessageissentwhenthezonerestores.
This allows the Central Station to count the number of devices per zone.
END - SelectENDtostoptheWalkTest.WhentheWalkTestendsora20-minute
time-outexpires,analSensorResetoccurs.TheSystemTestEndmessageis
senttothereceiveralongwithVerifyandFailmessagesforeachzoneundertest.
Faulted zones then display on the keypad.
CKIN:XXX/ZZZ END
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a
supervisioncheck-inmessage.
• Thenumberofzonesthatcheckin.(XXXintheexample).
• Thetotalnumberofwirelesszonesprogrammedforsupervisionthatshould
checkin.(ZZZintheexample).
END -SelectENDtostoptheWirelessCheck-inTest.Whenthetestendsor
a20-minutetime-outexpires,normalwirelesszoneprocessingreturns.If
alltransmitterscheck-in,bothnumbersmatchwithinthree(3)minutes.Ifa
transmitterhasmultiplezones(1101,1114,etc.),allzonesareincludedinthe
counts. Failed wireless zones display on the keypad.
TEST END WARNING
Test End Warning
Whenveminutesremainonthe20minuteWalkTesttimer,thekeypaddisplays
TESTENDWARNING.Ifnoadditionaltestzonetripsoccur,thetestendsanda
nalSensorResetautomaticallyoccurs.TheSystemTestEndmessageissentto
thereceiveralongwithVerifyandFailmessagesforeachzoneundertest.Faulted
zones then display on the keypad.
Note: Key fobs do not send failure messages in order to prevent functioning key
fobsthatarenotpresentatthetimeofthetestfrombeingreportedasMISSING.
SOUTH LOBBY
Failed Zones Display
ZONE: 10 -FAIL
Foreachzonethatdidnottrip(failed)atleastonceduringtheWalkTest,all
keypads with matching Area Display programming display the zone name and
numberandbuzzforonesecond.Anyselected(*FI*PN*SV)24-hourzonethat
is faulted at the end of the Walk Test displays a trouble condition for that zone
regardless of the message programmed for the open or short condition of the zone
and a zone trouble is sent to the receiver. Press the COMMAND key to display the
next failed zone.
Note:FortheWirelessCheck-inTest,failedwirelesszonesdisplayonlyonthe
keypad.ZoneVerify/Failreportsarenotsenttothecentralstationreceiverforthe
wirelesscheck-intest.
21.5 Keypad Speaker Operation
WhenusingLCDKeypads,thepanelprovidesdistinctspeakertonesfromthekeypadforFire,Burglary,
ZoneMonitor,andPrewarnevents.Thelistbelowdetailstheconditionsunderwhichthespeakeristurned
on and off for each event.
Fire On-FirezonealarmandBellOutputorFireBellOutputisON.
Off -AlarmSilence.
Burglary On -BurglaryzonealarmandBellOutputorBurglaryBellOutputisON.
Off-AlarmSilence.
Zone Monitor On-Onetimeonlywhenamonitoredzoneistripped.
Off-Afteronetone.
Prewarn On-DuringEntryDelay.
Off-WhenEntryDelayexpires.