CommuniCaTion
3.3
ACCNT NO: 12345
Account Number
Enter the account num ber sent to the receiver.
DD, NET - The range of account numbers for Digital Dialer and Network is 1 to
65535. For account numbers of four digits or less, you do not have to enter leading
zeros. The panel automatically right justies the account number.
4-2, M2E, and CID - The account number range for these formats is 1 - 9999.
3.4
XMIT DELAY: 30
Transmit Delay
Enter the number of seconds (15 to 45 seconds) the panel waits before sending
burglary alarm reports to the receiver. The bell and relay outputs are not delayed
during this period. Program Burglary Outputs for steady, and set Abort Reports to
YES if Opening and Closing reports are not being sent. Enter 0 (zero) to disable this
function. The default is 30.
If the area where the alarm occurred is disarmed during the Transmit Delay time,
only an Abort Report (S45) message is sent to the receiver. If the area where the
alarm occurred is disarmed after the alarm message is sent to the receiver but
before the Bell Cutoff time expires, even if the alarm was silenced, an Alarm
Cancelled (S49) message is sent. The Alarm Cancelled report cannot be disabled.
Note: For UL Installations, the combined Transmit Delay (Abort Window) and
Entry Delay must not exceed one (1) minute.
3.5
DTMF NO YES
DTMF
YES enables tone dialing. NO enables rotary dialing.
3.6
DFR TEST NO YES
Defer Test Time
Select YES to allow the programmed test report to be deferred if the panel
communicates with a receiver within the time set in Test Frequency. Select NO to
send the test report as programmed in Test Frequency regardless of previous panel
communication.
3.7
EVENT MGR: SND
Event Manager
This option species when non-alarm reports are sent to the receiver. This selection
does not affect zone alarm, zone trouble, zone restoral, supervisory, or serviceman
messages. Closing reports are not delayed if you have programmed a YES for the
Bell Test option.
SND DLY KEEP
SND - All reports are sent to the receiver as they occur.
DLY - All non-alarm reports are held until the panel memory buffer contains 40
events on the XRSuper6, 66 events on the XR20, and 100 events on the XR40, or
until the panel’s next communication with the receiver.
Note: If BELL TEST is YES, Closing reports are not delayed.
Note: NET communication does not delay any messages.
KEEP - All non-alarm reports are held in the panel memory buffer until they are
overwritten by new activity. You can view the contents of the buffer using the DMP
Remote Link™ software, or the Display Events function in the User Menu. Contact
ID, Modem IIe, and 4-2 formats do not delay reports but send them as they occur.
Time update from the SCS-1R Receiver: The XRSuper6/XR20/XR40 requests a time
update each time (once each day maximum) the panel contacts the receiver. The
Update Time to Panel option must be set to YES. In addition, the central station
automation system must be congured to update the time in the receiver at least
once each day.
3.8
TEST FREQ: 0
Test Frequency
Allows you to set how often the panel test report is sent to the receiver. Enter from
1 to 60 days. Enter zero to disable the test report.