36
STATUS LIST
Status List
15.1 Status List
This function allows you to select the zone alarms and troubles, and system monitor
troubles displayed at the keypads. The Status List function operates automatically when
the keypad is not performing any other function.
The keypad stays in the Status List until the user arms or disarms or selects a menu option.
Status List al ternates with the Armed Status on keypad addresses selected in the Menu
Display - Armed Status section. You can choose to have Sys tem Monitor troubles placed in
the list, the differ ent zone types placed in the list, and at which keypad addresses they dis-
play.
To select a keypad, enter the device number (keypad address) using the digit keys on the
keypad. When a keypad is selected, an asterisk appears next to the keypad address. Enter
the number again to deselect the keypad. Press the COMMAND key to display the next set
of keypads (9 through 16). Refer to the Multiple Displays section at the beginning of this
document.
15.2 Display Keypads
This option denes which keypad ad dresses display the various status information. Any
combina tion of addresses can be en tered to display the status items that follow. If you do
not want a particular status item to dis play, do not enter any ad dresses.
15.3 System Monitor Troubles
Species the keypad addresses (1 through 16) where any trouble on a System Monitor
dis plays. The System Monitors include the following:
• AC Power
• Battery Power
• Closing Check
• Panel Box Tamper
• Phone Line 1
• Phone Line 2 (requires the 893A Dual Phone Line Module)
• Wireless Receiver Trouble
• Wireless Jamming Trouble or Alarm
The System Monitor name is placed in the Status List and the keypad steady trouble buzzer
sounds. The buzzer remains on until any keypad top row Select key is pressed. The name
remains in the list until the condition is re stored. The buzzer sounds at 10:00 am daily until
the system trouble is cleared from the Status List.
15.4 Fire Zones
Species the keypad addresses (1 through 16) where all re zone alarms and troubles
display. The zone name displays and, if it is a trouble condition, the keypad steady trouble
buzzer sounds. The buzzer remains on until any top row Select key is pressed and a user
code is entered. If a trouble condition remains in the display, the buzzer sounds at 10:00
am daily until the trouble is cleared from the Status List.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for
Fire:
On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence
15.5 Burglary Zones
Species the keypad addresses (1 through 16) where all burglary zone alarms and troubles
display. Bur glary zones in clude Night, Day, and Exit type zones. Burglary zone troubles
remain in the list until the zone restores. All keypads are selected by default.
For zone alarms, only the last burglary zone tripped re mains in the list. The alarm remains
in the list un til another burglary zone goes into alarm, any area of the system is dis armed,
or 10 minutes elapse without an alarm. This ensures that if a bur glary is in progress the last
zone tripped remains in the list even if the zone is restored.
The keypad buzzer sounds for one second on bur glary alarms.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for
Burglary:
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
You can further dene which keypad address shows a Burglary Zone event by entering that
area number in the Display Areas menu during Device Setup.
STATUS LIST
DISPLAY KEYPADS:
SYSTEM TROUBLES:
*1 *2 *3 *4
*5 *6 *7 *8
*9 *10 *11 *12
*13 *14 *15 *16
FIRE ZONES:
BURGLARY ZONES:
Commentaires sur ces manuels