Digital Monitoring Products XR150/XR350/XR550 Series Programming Guide
50
ZONE INFORMATION
18.12 Alarm Action
This option allows you to change any Zone Type standard denitions. When the Zone
Type is specied, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a non-24-hour
zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that is
always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone initiates an alarm, the panel performs a Sensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the reset, an
alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is repeated and a
zone fault report is sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.
18.13 Disarmed Open
Denes the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to dene: Report to transmit, Relay Output to
activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press COMMAND to continue.
18.14 Report to Transmit
Press any Select key to display the following report options: A, T, L, S, C, and - (dash).
ALARM - Select A to send an alarm report to the receiver and activate the bell output
according to zone type. The zone name appears in the panel alarmed zones and status
lists.
TROUBLE - Select T to send a trouble report to the receiver. The zone name appears in
the panel alarmed zones and status lists.
Note: UL requirements prevent the Alarm (A) and Trouble (T) action for Fire (FI), and
Fire Verify (FV) zone types from being changed.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell output
activates and the zone name appears in the panel alarmed zones and status lists.
- (Dash) - When you select a – (dash), reports are NOT sent to the receiver. The bell
output does not activate and there is no display in the panel alarmed zones or status
list. Only the relay output selected in the next section operates.
DOOR PROPPED - Selecting D allows the following operation: The time programmed into
ENTRY DLY 4 in the System Option section begins to count without displaying on keypad.
If the time expires and the zone has not returned to normal, the keypad trouble buzzer
starts and CLOSE THE DOOR appears on the keypads programmed into the PREWARN
ADDRESS section. The time programmed into ENTRY DLY 4 begins to count down again
internally. If the time expires a second time and the zone has not returned to normal, a
fault report is sent to the receiver and the zone name - OPEN message displays on the
keypads until a code is entered. The bell output does not activate for the Door Propped
operation.
SILENCE/RESET - Select S when the zone (not FI, SV, or FV) is connected to a DMP Model
303 Silence/Reset switch, the zone can be used to silence the alarm bell and perform a
sensor reset without using a keypad. A report is NOT sent to the receiver except for the
bell silence report.
CANCEL AMBUSH - Select C for the zone to cancel the Early Morning Ambush timer and
stop an Ambush message from being sent to the receiver. Faulting the zone takes the
place of a second user code being entered at the keypad and is only available for non-
re type zones. Area assignment for the zone does not affect this option. See Early
Morning Ambush in Area Information programming .
18.15 Output Number
You can specify any of the Relay Outputs on the panel to be activated by a zone
condition (1 to 6, 500 to 999 if Model 716 used, D1 to D16, G1 to G20). The output
can be activated regardless of the report to transmit or whether or not the zone is
programmed as local. An output activated by an armed zone is turned off when the zone
area is disarmed by a user.
To enter an output number, press a top row Select key followed by the output number.
Press the COMMAND key.
18.16 Output Action
Entering an Output Number displays this option. This option allows you to assign an
output action to the relay: Steady, Pulse, Momentary, or Follow.
Note: Some wireless devices whether powered using an AC adaptor or a battery, ignore
some output action programming.
ALARM ACTION . . . .
DISARMED OPEN
MSG: TROUBLE
A T L -
D S C
OUTPUT NO: 0
OUTPUT: NONE