Digital Monitoring Products XR100 Series Installation Guide
2
INTRODUCTION
XR100 Series Installation Guide Digital Monitoring Products
3
INTRODUCTION
Panel Features
2.1 Description
The DMP XR100 Series Command Processor™ Panel is a versatile 12 VDC, combined access control, burglary, and re
communicator panel with battery backup. The XR100 Series provides eight on-board burglary zones and two on-board
12 VDC Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors,
relays, or other latching devices. The XR100 Series can communicate to one or two DMP SCS-1/SCS-1R Receivers
using digital dialer or network communication, or to non-DMP receivers using the Contact ID format.
2.2 Zone Expansion
Up to 142 additional zones are available on the XR100 Series using DMP LCD keypad remote zone capability and
zone expansion modules. The panel keypad data bus supports up to sixteen supervised device addresses with each
address supporting up to four programmable expansion zones.
Up to 100 zones are available using the on board LX-Bus and any combination of single, four, eight, or 16-zone
expansion modules and single-zone LX-Bus™ detectors.
Note: Do not use shielded wire for LX-Bus or Keypad Bus circuits.
2.3 Output Expansion
In addition to the two SPDT relays and four open collector outputs on the XR100 Series, you can also connect up to
25 Model 716 Output Expansion Modules. These modules can provide an additional 100 programmable SPDT relays.
The XR100 Series provides 100 Output Schedules you can use for programming the 716 to perform a variety of
annunciation and control functions. You can also assign the 716 outputs to any panel Output Options such as Fire
Alarm, Communication Fail, or Phone Trouble Outputs. Refer to the 716 Installation Guide (LT-0183).
The LX-Bus™ also supports the Model 717 Graphic Annunciator Module. Each 717 module supplies 20 switched ground
outputs that follow the state of their assigned zones.
Note: The 717 supports the rst eight Keypad Bus addresses. To follow Keypad Bus addresses nine through 16, install
multiple 716 modules. Refer to the 717 Installation Guide (LT-0235) and 716 Installation Guide (LT-0183).
2.4 Central Station Communication
You can program the XR100 Series panel for reporting to one or two DMP SCS-1/SCS-1R Receivers using digital
dialer or network communication. The panel can also communicate to non-DMP receivers using the Contact ID
communication format. The XR100 Series connects at the premises to a standard RJ31X or RJ38X telephone jack. Use
the DMP 893A Dual Phone Line Module when connecting the XR100 Series panel to two separate phone lines in re or
burglary applications.