Digital Monitoring Products XR100 Series Installation Guide
24
COMPLIANCE
XR100 Series Installation Guide Digital Monitoring Products
25
COMPLIANCE
UL 609 Specications
Police Station Connected and Local Burglar Alarm Units and Systems
26.1 Grade A Mercantile
For Grade A Mercantile and Police Station Connect operation the Model XR100 Series must be mounted in a Grade A
Attack Resistant Housing, (DMP Model 350A).
26.2 Entry Delay
The maximum entry delay used must not be more than 60 seconds when using the Model 350A Grade A housing. See
the XR100 Series Programing Guide (LT-0896).
26.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the XR100 Series Programming Guide
(LT-0896).
26.4 Mercantile Safe and Vault
When the DMP Model 350A housing is used, the XR100 Series provides operation as a mercantile safe and vault alarm.
Bell Supervision and wiring must be in accordance with UL 681. When the XR100 Series is mounted outside the safe
or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should be used.
26.5 Grade A Bell
A Grade A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
UL 294 Specications
Access Control System Units
27.1 Panel Designation
The XR100 Series panels are designated stand alone units.
27.2 Tamper Protection
For UL Listed Access Control installations, a tamper switch must be used.
27.3 Compatible Devices
The following devices are compatible with the XR100 Series panels.
Access Control
733 Wiegand Interface Module Proximity reader connector
734 Wiegand Interface Module Proximity reader connector
OP-08CB Motion Detector Infrared sensor
* PB-2 REX Button Exit control push button
PP-6005B Proxpoint Plus® Reader Proximity reader
MP-5365 Miniprox® Reader Slimline proximity reader
PR-5455 ProxPro® II Reader Long range reader with sounder
MX-5375 Maxi-Prox™ Reader Long range reader compatible with 1351 Prox Pass
* This device has not been investigated by UL and shall not be used in UL installations.
Universal UL and NFPA Fire Alarm Specications
28.1 Introduction
The programming and installation specications contained in this section must be completed when installing the
Model XR100 Series in accordance with any of the UL or NFPA re standards. Additional specications may be
required by a particular standard.
28.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.