Digital Monitoring Products XR100 Series Installation Guide
24
COMPLIANCE
XR100 Series Installation Guide Digital Monitoring Products
25
COMPLIANCE
28.3 Transformer
A wire-in transformer should be used. Use the Model 322 wire-in 16 VAC 56 VA transformer or Model 327 plug-in
16 VAC 50 VA transformer installed inside an ES501 Enclosure with all wiring in conduit. The transformer must be
mounted within 20 feet of the panel and connected by conduit.
28.4 End-of-Line Resistor
The DMP Model 310 1k Ohm EOL resistor should be used on all 1k Ohm EOL re zones.
28.5 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See the XR100 Series
Programming Guide (LT-0896).
28.6 Fire Display
The Status List Display must include at least one keypad that displays troubles and alarms on re type zones. See
the XR100 Series Programming Guide (LT-0896).
28.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unless that phone number is specically provided for that purpose.
28.8 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by the
installing alarm company and frequent testing by the end user is essential. Offering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
28.9 Audible Alarm
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones should not
be programmed as “N”. See the XR100 Series Programming Guide (LT-0896).
28.10 Fire Zone Programming
If a retard delay is used on a waterow zone, it cannot exceed 90 seconds and any retard delay in the waterow
initiating devices must be subtracted from the 90 seconds allowed. See the XR100 Series Programming Guide
(LT-0896). The retard delay should not be used on a zone with smoke detectors.
28.11 Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Style D zones to the
Model XR100 Series. See the 869 Installation Guide (LT-0186) and sections 20.2 and 28.2 of this guide for wiring
information.
28.12 Video Option
The Video option must be selected as NO when any re protection is connected to the XR100 Series. See the XR100
Series Programming Guide (LT-0896).
28.13 UL Listed Receivers
Use the DMP SCS-1/SCS-1R (SDLC), Sur-Gard SG-HLR2-DG (CID), FBII CP220PB (CID), and Osborne-Hoffman Quick-Alert
(CID) receivers.
28.14 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. See the XR100 Series
Programming Guide (LT-0896).
28.15 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes. See the XR100 Series Programming Guide (LT-0896).
28.16 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication (FV)
zone type. See the XR100 Series Programming Guide (LT-0896).