COMPLIANCE
XR100 Series Installation Guide Digital Monitoring Products
27
COMPLIANCE
30.2 Audible Devices
At least one listed audible device rated to operate over the voltage rate of 11.7 VDC to 12.8 VDC and rated at 85 DB
minimum must be used.
30.3 Auxiliary Circuits
At least one re alarm initiating device shall be used on the system. If the voltage for the device is applied by the
control unit the re alarm initiating device shall be rated to operate over the range of 11.5 VDC to 12.7 VDC.
30.4 Bell Cutoff
The Bell Cutoff time cannot be less than ve minutes. See the XR100 Series Programming Guide (LT-0896).
30.5 Detect Wireles Jamming
The Detect Wireless Jamming option must be programmed YES. See the XR100 Series Programming Guide (LT-0896).
California State Fire Marshal Specications
31.1 Bell Output Denition
The Model XR100 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal, or California School Code on re alarms. See the XR100 Series Programming Guide (LT-0896).
New York City (MEA) Specications
32.1 Introduction
The programming and installation specications contained in this section must be completed when installing the
XR100 Series panel for New York City (MEA) re alarm installations that provide a digital dialer with network IP
communication as backup. Fire alarm installations that use two digital dialer telephone lines do not need to comply
with these specications.
32.2 Digital Dialer and Network Communication
When used with a central ofce communicator or a transmitter, the installation and operation of the equipment and
devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as the primary communicator
(using telephone line) with network IP communication as backup or secondary means of communication. It shall
have the capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
detection alarm, sprinkler waterow alarm, supervisory signal indications and trouble indications.
32.3 Wiring
All wiring must be in accordance with NEC, ANSI, and NFPA 70. All network cabling must be installed in accordance
with NFPA 70 for communication circuits.
32.4 Communication Programming
For digital dialer communication with supervised network backup, program the following:
COMM TYPE = NET
SECOND LINE = DD
RECEIVER 1
ALARMS = YES
FIRST PHONE NUMBER = Central Station Receiver Phone Number
RECEIVER 2
ALARMS = YES
FIRST PHONE NUMBER = Central Station Receiver Phone Number
See the XR100 Series Programming Guide (LT-0896).
32.5 Additional Requirements
Program and install the equipment to comply with NFPA basic re requirements. Refer to the Universal UL and NFPA